AC 2500-6

Product: CUMMINS Alternator: ECO 46-1L/4 A - 60Hz Regelsystemen: DSE 7320
Over Product
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
Certificaten
  TS ISO 8528
  CE
  SZUTEST
  2000/14/EC
Algemene kenmerken
Modelnaam AC 2500-6
Frequentie (HZ) 60
Brandstoftype Diesel
Motormerk en -model CUMMINS - QSK 60-G7 - 60Hz
Alternatormerk en -model Mecc Alte - ECO 46-1L/4 A - 60Hz
Configuratiescherm Model DSE 7320
Cabine AK 99 - External Removable Silencer
3 Fasen, 60 Hz, PF 0.8
Spanning Stand-by vermogen (ESP) Prime Power (PRP) Standby Amper
kVA kW kVA kW
480/277 2500 2000.00 2269 1815.20 3007.12
380/220 2375 1900.00 2160 1728.00 3608.55
Stand-by vermogen (ESP) : Het wordt gebruikt om te voldoen aan de variabele elektrische belastingvereiste in geval van uitval van de betrouwbare netvoeding. ESP voldoet aan ISO 8528-1 Overbelasting is niet toegestaan.

Prime Power (PRP) : Wordt gedefinieerd als het continue bedrijfsvermogen onder variabele belasting. PRP voldoet aan ISO 8528-1 10% overbelasting kan elke 12 uur worden gedaan.
Motorkenmerken
Motor CUMMINS
Motor model QSK 60-G7 - 60Hz
Aantal Cilinders En Gebouw 16 cylinders - V type
Boor En Slag mm 159 X 190
Totale Verplaatsing L 60.2
Aspiratie Turbo Charged and One Pump Two Loop
Compressieverhouding 14.5:1
Nominale snelheid d/dk 1800
Olie capaciteit L 280
Stand-by vermogen (kW/HP) 2180/2922
Brandstoftype
Diesel
Type brandstofpomp
Cummins PT
Governor-systeem
Electronic
Bedrijfsspanning (Vdc)
24 Vdc
Koelmethode
Water Cooled
Koelvloeistofcapaciteit (alleen motor / met radiator) (lt) 682
Luchtfilter
Dry Type
Brandstofverbruik bij eerste 100% belasting (lt / uur) 471
Brandstofverbruik primair 75% belasting (lt / uur) 360
Brandstofverbruik bij eerste 50% belasting (lt / uur) 254
Dynamo specificaties
Fabrikant Mecc Alte
Alternatormerk en -model ECO 46-1L/4 A - 60Hz
Frequentie (HZ) Hz 60
Kracht (kVA) kVA 2200
Ontwerp   Brushless
Spanning V 400
Fase 3
Automatische spanningsregelaar DER1
Voltage regulatie (+/-) 0.5
Isolatiesysteem H
Bescherming IP23
Nominale vermogensfactor 0.8
Gewicht dynamo (Kg) 3805
Koellucht (m³/min) m3 162
Grootte en gewicht
Open Type Droog gewicht (kg.)
(kg.)
Lengte
(mm.)
Breedte
(mm.)
Hoogte
(mm.)
Inhoud brandstoftank (lt.) (Lt.)
15500 5710 2280 3220 2000
Cabin Group Droog gewicht (kg.)
(kg.)
Lengte
(mm.)
Breedte
(mm.)
Hoogte
(mm.)
Inhoud brandstoftank (lt.) (Lt.)
AK 99 - External Removable Silencer
TBD 9000 2800 3307 2200
Standaardfuncties
Heavy duty, water cooled diesel engine
Radiator with mechanical fan
Protective grille for rotating and hot parts
Electric starter and charge alternator
Starting battery (with lead acid) including rack and cables
Engine coolant heater
Steel base frame and anti-vibration isolators
Spare external fuel tank (open set)
Flexible fuel connection hoses
Single bearing, class H alternator
Industrial exhaust silencer and steel bellows supplied separately
Static battery charger
Manual for application and installation
Generator hardware-opties
TRANSFER SWITCH
- Three or four pole motor operated circuit breaker
- Four Pole Contactor
- Three Pole Contactor
OTHER ACCESSORIES
- Tool kit for maintenance
- Inlet and outlet acoustic baffles
- Inlet and outlet motorised louvers
- Automatic transfer switch
- Main Fuel Tank
- Supplied with oil and coolant - 30 °C
- Low and high fuel level alarm
- Electrical oil drain pump
- Automatic or manual fuel filling system
- Duct adapter ( on radiator)
- Enclosure: weater protective or sound attenuated
- Residential silencer
CONTROL SYSTEM
- Remote communication with modem
- Alarm output relays
- Charge Ammeter
- Earth fault, single set
- Remote relay output
- Paralel system with mains.
- Automatic synchronising and power control system ( multi gen-set
Parallel )
- Remote annunciator panel
- Transition synchronization with mains
ENGINE
- Oil heater
- Fuel-Water Seperator Filter
- Remote Radiator Cooling
ALTERNATOR
- Main line circuit breaker
- Over sized alternator
- Anti-Condensation Heater
Regelsystemen: DSE 7320
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Apparaten
DSE, model 7320 Auto Mains Failure control module Static battery charger Emergency stop push button and fuses for control circuits
Structuur en verf
Comonents installed in sheet steel enclosure.
Phosphate chemical, pre-coating of steel provides corrosion resistant surface
Polyester composite powder topcoat forms high gloss and extremely durable finish
Lockable hinged panel door provides for easy component access
Montage
Control panel is mounted generating set baseframe on robust steel stand or power module. Located at side of generating set with properly panel visibility.
Generator regeleenheid
The DSE 7320 conrol module is a standard addition to our generator sets from 220 kVA upwards and it has been designed to start and stop diesel andgas generating sets that include electronic and non electronic engines.
The DSE 7320 includes the additional capability of being able to monitor a mains (utility) supply and is therefore suitable for controlling a standby generating set in conjunction with an automatic transfer switch.
The DSE7320 also indicates operational status and fault conditions, automatically shutting down the generating set and indicating faults by means of its LCD display on the front panel.

Standaardfuncties
Microprocessor controlled
- 132 x 64 pixel LCD display makes information easy to read
- Front panel programming and also via PC software
- Soft touch membrane keypad and five key menu navigation
- Remote communications via RS232, RS485 and ethernet.
- Event logging (50) showing date and time
- Multiple date and time engine exercise mode and maintenance scheduler
- Engine block heater control.
- Controls; stop, manuel, auto, test, start, mute lamb test/transfer to generator, transfer to mains, menu navigation.

Meetindicatoren
ENGINE
Engine speed
Oil pressure
Coolant temperature
Run time Battery volts
Engine maintenance due

GENERATOR
Voltage (L-L, L-N)
Current (L1-L2-L3)
Frequency
Earth current
kW
Pf
kVAr
kWh, kVAh, kVArh
Phase sequence

MAINS
Voltage (L-L, L-N)
Frequency
Beveiligingscircuits
WARNING
Charge failure
Battery under voltage
Fail to stop
Low fuel level (opt.)
kW over load
Negative phase sequence
Loss of speed signal

PRE-ALARMS
Low oil pressure
High engine temperature
Low engine temperature
Over /Under speed
Under/over generator frequency
Under/over generator voltage
ECU warning

SHUT DOWNS
Fail to start
Emergency stop
Low oil pressure
High engine temperature
Low coolant level
Over /Under speed
Under/over generator frequency
Under/over generator voltage
Oil pressure sensor open
Phase rotation

ELECTRICAL TRIP
Earth fault
kW over load
Generator over current
Negative phase sequence


Optie Kenmerken
High oil temperature shut down
Low fuel level shut down
Low fuel level alarm
High fuel level alarm

EXPANSION MODULES
Editional LED module (2548)
Expension relay module (2157)
Expansion input module (2130)
Standaarden
Elecrical Safety / EMC compatibility

BS EN 60950 Electrical business equipment
BS EN 61000-6-2 EMC immunity standard
BS EN 61000-6-4 EMC emission standard
Elektronische acculader
Battery charger is manufactured with switching-mode and SMD technology and it has high efficincy.
Battery charger models' output V-I characteristic is very close to square
2405 has fully output shot circuit protection and ıt can be used as a current source.
2405 charger has high efficiency, long life, low failure rate, light weight and low heat radiated in accordance with linear alternatives.
The charger is fitted with a protection diode across the output.
Charge fail output is available.
Connect charge fail relay coil between positive output and CF output.
Input: 196-264V.
Output: 27,6V 5A or 13,8V 5A.
Cabine: AK 99 - External Removable Silencer
1. Steel structure made from steel sheet and steel profiles.
2. Canopy and panels made from powder coated sheet steel.
3. Emergency stop push button.
4. Control panel is mounted on the baseframe located at the back of the  Generator set.
5. Cables out locations are back of the canopy.
6. Corrosion.resistant locks and hinges.
7. Oil could be drained via valve and a hose.
8. Exhaust system on the canopy.
9. Special large access doors for easy maintanance.
10. The cap on the canopy provides easy accsess to radiator cap.
11. Lifting points similar to ISO container, located on each top corner of the Canopy.
12. Sound proofing materials.
13. Fuel tank is at front of the canopy ,easy access to the fuel tank via lockable door.
14. Integrated ladder built in toside of the canopy allows access to the top of the canopy.
Over Product
Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
Standaardfuncties
Compact footprint, low profile design. 
Enclosure, generator set, exhaust system and fuel tank are pre-ssembled, pre-integrated and shipped as one package 
Body made from steel components treated with polyester powder coating 
Fire retardant foam insulation 
Easy access to all service points 
Exhaust system inside canopy 
Large doors on each side 
Control panel viewing window in a lockable access door 
Emergency stop push button mounted on enclosure exterior 
Cooling fan and battery charging alternator fully guarded 
Fuel fill and battery can only be reached via lockable access doors. 
Lifting points on the top of canopy and base frame 
Customer options available to meet your applications needs. 
Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been aproved by the notified body Szutest

Kastserie Model AK 99 - External Removable Silencer
Breedte mm. 2800
Lengte mm. 9000
Hoogte mm. 3307
Inhoud brandstoftank (lt.) Lt. 2200