AC 55

Product: CUMMINS Alternator: ECP 32-1M/4 C Regelsystemen: DSE 6120
Over Product
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
Certificaten
  TS ISO 8528
  CE
  SZUTEST
  2000/14/EC
Algemene kenmerken
Modelnaam AC 55
Frequentie (HZ) 50
Brandstoftype Diesel
Motormerk en -model CUMMINS - S3.8-G6
Alternatormerk en -model Mecc Alte - ECP 32-1M/4 C
Configuratiescherm Model DSE 6120
Cabine AK 30
3 Fasen, 50 Hz, PF 0.8
Spanning Stand-by vermogen (ESP) Prime Power (PRP) Standby Amper
kVA kW kVA kW
400/231 55 44.0 50 40.0 79.39
Stand-by vermogen (ESP) : Het wordt gebruikt om te voldoen aan de variabele elektrische belastingvereiste in geval van uitval van de betrouwbare netvoeding. ESP voldoet aan ISO 8528-1 Overbelasting is niet toegestaan.

Prime Power (PRP) : Wordt gedefinieerd als het continue bedrijfsvermogen onder variabele belasting. PRP voldoet aan ISO 8528-1 10% overbelasting kan elke 12 uur worden gedaan.
Motorkenmerken
Motor CUMMINS
Motor model S3.8-G6
Aantal Cilinders En Gebouw 4 cylinders - in line
Boor En Slag mm 97 X 128
Totale Verplaatsing L 3.8
Aspiratie Turbo Charged
Compressieverhouding 17.5:1
Nominale snelheid d/dk 1500
Olie capaciteit L 11
Stand-by vermogen (kW/HP) 53.6/71.9
Prime Power (kW/HP) 48.7/65.3
Blokverwarmingshoeveelheid
1
Blokkeer verwarmingsvermogen (Watt) 750
Brandstoftype
Diesel
Injectietype en systeem
Direct
Type brandstofpomp
Bosh In-Line
Governor-systeem
Mechanic
Bedrijfsspanning (Vdc)
12 Vdc
Batterij en capaciteit (aantal / Ah) 1x66
Laaddynamo (A)
40
Koelmethode
Water Cooled
Koelventilatorluchtstroom (m³ / min) 82
Koelvloeistofcapaciteit (alleen motor / met radiator) (lt) 7/14.5
Luchtfilter
Dry Type
Brandstofverbruik bij eerste 100% belasting (lt / uur) 12.8
Brandstofverbruik primair 75% belasting (lt / uur) 9.5
Brandstofverbruik bij eerste 50% belasting (lt / uur) 6.5
Dynamo specificaties
Fabrikant Mecc Alte
Alternatormerk en -model ECP 32-1M/4 C
Frequentie (HZ) Hz 50
Kracht (kVA) kVA 50
Ontwerp   4 Pole,  Brushless
Spanning V 400
Fase 3
Automatische spanningsregelaar DSR
Voltage regulatie (+/-) 1
Isolatiesysteem H
Bescherming IP23
Nominale vermogensfactor 0.8
Gewicht dynamo (Kg) 186
Koellucht (m³/min) m3 15.7
Grootte en gewicht
Open Type Droog gewicht (kg.)
(kg.)
Lengte
(mm.)
Breedte
(mm.)
Hoogte
(mm.)
Inhoud brandstoftank (lt.) (Lt.)
890 1780 950 1290 130
Cabin Group Droog gewicht (kg.)
(kg.)
Lengte
(mm.)
Breedte
(mm.)
Hoogte
(mm.)
Inhoud brandstoftank (lt.) (Lt.)
AK 30
1160 2472 1006 1537 130
Standaardfuncties
Water cooled, Diesel engine
Radiator with mechanical fan
Protective grille for rotating and hot parts
Electric starter and charge alternator
Starting battery (with lead acid) including rack and cables
Engine coolant heater
Base frame design incorporates an integral fuel tank and anti-vibration isolators
Flexible fuel connection hoses
Single bearing, class H alternator
Industrial exhaust silencer and steel bellows supplied separately(for open sets)
Static battery charger
Manual for application and installation
Generators Sets’ voltage and frequency regulation comply with ISO 8528-5 Generators Sets’ can take 100% load at one step according to NFPA110
Generator hardware-opties
ENGINE
• Remote Radiator Cooling
• Fuel-Water Seperator Filter
• Low water level alarm
• Oil heater

ALTERNATOR
• Anti-Condensation Heater
• Over sized alternator
• Main line circuit breaker

CONTROL SYSTEM
• Remote annunciator panel
• Earth fault, single set
• Charge Ammeter

TRANSFER SWITCH
• Three or four pole contactor
• Three or four pole motor operated circuit breaker

OTHER ACCESSORIES
• Main Fuel Tank
• Automatic or manual fuel filling system
• Manual oil drain pump
• Low and high fuel level alarm
• Residential silencer
• Enclosure: weater protective or sound attenuated
• Duct adapter ( on radiator)
• Inlet and outlet motorised louvers
• Inlet and outlet acoustic baffles
• Trailer
• Tool kit for maintenance
• 1500/3000 hours maintenance kit
• Double wall chassis
• Supplied with oil and coolant - 30 °C
• Battery isolating switch
Regelsystemen: DSE 6120
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Apparaten
●DSE, model 6120 Auto Mains Failure control module.
●Battery charger input 198-264 volt, output 27,6 V 5 A (24 V) or 13,8 Volt 5A (12V)
●Emergency stop push button and fuses for control circuits.
Structuur en verf
●Components installed in sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion resistant surface. Polyester composite powder topcoat forms high gloss and extremely durable finish. Lockable and hinged panel door provides easy access to components.
Montage
Control panel is mounted on baseframe with steel stand. Located at the right side of the generator set (When you look at the Gen.Set. from Alternator)
Generator regeleenheid
The DSE 6120 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant temperature running hours and battery volts.
Module monitors the mains supply and switch over to the generator when the mains power fails.
The DSE6120 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving true first up fault condition of Gen. Set failure.The LCD display indicates the fault.

Standaardfuncties
●Microprocessor controlled.
●LCD display makes information easy to read.
●Automatically transfers between mains (utilty) and generator power.
●Manual programming on front panel.
●User-friendly set-up and button layout.
●Remote start.
●Event logging (50) showing date and time.
●Controls: Stop/Reset, Manual, Auto, Test, Start, buttons. An additional push button next to the LCD display is used to scroll through the modules' metering displays.

Meetindicatoren
ENGINE
●Engine speed.
●Oil pressure.
●Coolant temperature.
●Run time.
●Battery volts.
●Configurable timing.

GENERATOR
●Voltage (L-L, L-N).
●Current (L1-L2-L3).
●Frequency.
●Gen. Set ready.
●Gen. Set enabled.

MAINS
●Mains ready.
●Mains enabled.
Beveiligingscircuits
WARNING 
●Charge failure. 
●Battery Low/High voltage. 
●Fail to stop. 
●Low /High generator voltage. 
●Under /Over generator frequency. 
●Over /Under speed. 
●Low oil pressure. 
●High coolant temperature. 

SHUT DOWNS 
●Fail to start.
●Emergency stop. 
●Low oil pressure. 
●High coolant temperature. 
●Over /Under speed. 
●Under/over generator frequency. 
●Under/over generator voltage. 
●Oil pressure sensor open. 
●Coolant temperature sensor open. 

ELECTRICAL TRIP 
●Generator over current.


Optie Kenmerken
●Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)
●Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).
Standaarden
●Elecrical Safety / EMC compatibility
●BS EN 60950 Electrical business equipment.
●BS EN 61000-6-2 EMC immunity standard.
●BS EN 61000-6-4 EMC emission standard
Elektronische acculader
● Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency.
● Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volt and 27,6 V for 24 V . Input 198 - 264 volt AC.
● The charger is fitted with a protection diode across the output.
● Connect charge fail relay coil between positive output and CF output.
● They are equipped with RFI filter to reduce electrical noise radiated from the device.
● Galvanically isolated input and output typically 4kV for high reliability.
Cabine: AK 30
1. Steel structures 
2. Emergency stop push button 
3. Control panel is right side of the set. 
4. Corrosion.resistant locks and hinges 
5. Base frame .fuel tank. 
6. Lockable, large doors on each side. 
7. Lifting Points
Over Product
Sound–attenuated and Weather-protective Enclosures Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
Standaardfuncties
Compact footprint, low profile design. 
Enclosure, generator set, exhaust system and fuel tank are pre-ssembled, pre-integrated and shipped as one package 
Body made from steel components treated with polyester powder coating 
Fire retardant foam insulation 
Easy access to all service points 
Exhaust system inside canopy 
Large doors on each side 
Control panel viewing window in a lockable access door 
Emergency stop push button mounted on enclosure exterior 
Cooling fan and battery charging alternator fully guarded 
Fuel fill and battery can only be reached via lockable access doors. 
Lifting points on the top of canopy and base frame 
Customer options available to meet your applications needs. 
Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been aproved by the notified body Szutest

Kastserie Model AK 30
Breedte mm. 1006
Lengte mm. 2472
Hoogte mm. 1537
Inhoud brandstoftank (lt.) Lt. 130